|
7.0)
Water (drying): (page
5 of 5)
7.32) HVAC Systems: HVAC systems have passageways that
distribute clean air; be it fresh, makeup, cooled or heated, to
spaces that are generally occupied by persons, pets, belongs,
etc., while
bacteria,
mold (fungi) and contaminates foil the
passageways intention.
The remediation of HVAC systems after a water loss should
conform with
Sections 3.23.c,
3.23.d,
6.37,
6.37.a and
6.37.b, and the cleaning
and remediation standards and guidelines developed by the
National Air Duct Cleaning Association (NADCA).
7.33) Building Insulation:
The
remedial actions best suited for insulation after a water loss
would depend on the insulations style, characteristics, if there
is mold formation and the severity of the damages
caused by the water or moisture.
Mold (fungi) formation on
synthetic insulation is
generally due to organic soiling as affixed to the insulation
during construction, such as wood dust.
When water or secondary damage has jeopardized the insulations
R-value or fire rating, it should be replaced.
Blanket and batt insulation constructed from fiberglass has an
absorption rate of 0.05% or less and could be dried when moderately affected by water or moisture.
Additional remedial information on
building insulation can be found in
Section
6.21.n.
7.34) Drying Equipment:
The loss type (category/situation), surface types, and
post-condition (what is wet? and how wet is it?) would determine
the type and quantity of equipment needed to mitigate and
neutralize a water loss site.
When determining the quantity of equipment needed, the number of
rooms affected, the cubic feet of affected rooms, temperature,
humidity, rate of wicking, and moisture content of building
components and content items should be used as a basis.
When sizing dehumidification equipment, the water site drying
classifications in
Section 7.42 should be used as a
starting point.
Equipment left on site in an operable state for a considerable
amount of time should be inspected at least once in a 24-hour
period, and this should include, but not be limited to;
airmovers, dehumidifiers, generators, etc., and as conditions
improve, pieces of equipment should be removed.
7.35) Pumps:
Pumps are used to move water from one area to
another, and there are several types of pumps available to
achieve this goal:
- Low & high-pressure pumps
- Utility pumps
- Trash pumps
Utility pumps, a/k/a trench/ditch pumps are used to remove
standing water at several inches deep and some are submersible,
while pressure and trash pumps can remove water several feet
deep.
Low & high pressure pumps can be self-priming, or need priming
assistance.
Trash pumps are designed to move waters containing, mud, dirt,
stones, sticks, etc.
When pumping basements or lower levels after flooding, the
ground pressure outside the structure should be less than the
pressure inside the structure to prevent wall cracking or
collapse of the structure.
Recommended pumping procedures for
basements is available at
MisterFixIt.com/Flood.htm.
Pumps are rated at
gallons per hour (GPH) and lift, and the
U.S. gallons into cubic feet table would be helpful when
sizing pumps and calculating time frames.
Each pump has its application, and pumps should only be
used
for the applications they are designed for.
7.36) Extraction Equipment:
Extraction machines would be portable or truck
mount, and each has its benefits and limits.
Truck mount units offer large volume extraction, but are limited
on multi-level properties, while portable units are emptied more
often, yet are versatile in multi-level properties.
Extraction equipment should be in excellent working order and
spare parts, such as jets, couplings, valves, etc. should be on
hand.
7.37) Airmovers: There are several types
of airmovers designed specifically for structural drying:
- Turbofans
- Vortex Air Mover
- High Velocity Fans
- Low AMP Air Mover
Turbofans are designed at a low center of gravity to force air
along floor and wall surfaces, while axial fans are designed to
force a large volume of air across a large area.
Typically, one (1)
airmover per 300 SF minimum when drying, or three (3) airmovers
per one (1) dehumidifier --- depending on the dehumidifiers rate
of evaporation. (ref.
7.38)
Professional brand airmovers have varying accessories
available to aid with the drying process:
- Turbovents
- Turboduct
- Mini-Turbovents
- Flexible Ducting
When performing water
loss mitigation, residential box fans, circular fans, etc.
should not be used due to possible electrical shock or
electrocution.
7.38) Dehumidifiers: Dehumidifiers are
available in
refrigerant or
desiccant,
and the sizing of a refrigerant dehumidifier is based on grains (gpp) of
moisture it can draw
from the air in a 24-hour period, and a desiccant dehumidifier
is sized by the CFM, as illustrated in
Table 7-G and
Table 7-I.
Refrigerant (coil) dehumidifiers condense moisture from the
atmosphere onto chilled coils, while desiccant dehumidifiers
absorb the moisture from the air.
Standard refrigerant
dehumidifiers can operate at temperatures
as low as 67º F. Commercial dehumidifiers with hot gas
bypass operate as low as 40º F. Heat pump dehumidifiers operate down to 33º F.
And desiccant dehumidifiers operate down to 32º F
or lower.
The sizing of dehumidifiers (refrigerant and desiccant) is
listed within
Table 7-I, at the bottom of this page.
7.39)
Chemical Dispensers:
There are several applicators available to
dispense chemicals and cleaning agents:
- Ultra low volume (ULV) foggers
- Electric sprayers (airless)
- Hydo-Force injection sprayers
- Hand pump sprayers
- Trigger sprayers
Each dispenser is designed for a specific application such as;
room volume, surface area and within hidden cavities, and
dispensers should only be used for the applications they are
designed for.

|
Find
It Fast - With
The ...
LRGS
-
Navigational
Index
-
7.40) Injection Drying: Injection drying
equipment as manufactured by
Injectidry Systems and
Dri-Eaz
Products are pressure drying equipment that offer both positive
and negative pressure.
Injection drying
equipment when used in the right application and set up properly
will reduce the size of access hole penetrations in walls,
cabinetry, and flooring materials as well as reduce drying time
and prevent secondary damages.
7.41) Meters and Instruments: Contractors will use several
types of
meters
and instruments during mitigation:
- HydoSensor moisture probe
- Thermo-Hygrometer
- Moisture meter (penetrating and non-penetrating)
- Psychrometric calculator
- Dehumidifier calculator
- Thermal Imaging
The hydrosensor, penetrating meter and non-penetrating meter
operate as continuity meters and provides reading when a DC
volt circuit is completed. Thermal imaging camera uses infrared
technology, providing a heat differential.
7.42)
Loss Site (Drying) Classification:
During the evaluation of
a water loss site, technicians should determine the drying
classification as set forth by the IICRC. The classifying of a
water loss site by its evaporation rate, as affected by the
permeance of the structures building components and content
items, should provide technicians a starting point on dehumidification needed.
Table 7-A provides a brief listing of
building material permeance.
The four
IICRC water damage classifications are as follows:
Class 1: Slow Evaporation Rate:
Water losses that affect only part of a room or area, or losses
with lower
permeance/porosity materials (e.g.,
plywood,
particle board, structural wood,
VCT,
concrete). Little or no wet carpet
or cushion is present. Minimum moisture is absorbed by
materials, releasing moisture slowly.
Class 2: Fast Evaporation Rate:
Water losses that affect an entire room or
carpet and cushion. Water has
wicked up walls 12" - 24”. There
is moisture remaining in structural materials (e.g., plywood,
particleboard, structural wood, concrete).
Class 3: Fastest Evaporation Rate:
Water may have come from overhead. Ceilings, walls, insulation,
carpet, cushion and sub-floor in the entire area are
saturated.
Class 4: Specialty Drying Situations:
These consist of wet materials with very low
permeance/porosity (hardwood,
plaster,
brick, concrete, stone,
crawlspace). Typically, there are deep pockets of saturation,
which requires very low specific humidity.
Technicians should evaluate the water loss site to
determine their psychrometrics, materials permeance, etc., and
base their dehumidification on the cubic foot
of air within the affected areas based on the following steps:
Step 1:
Calculate the affected areas into cubic feet.
Step 2:
Determine water loss Class (#1, #2, #3, or #4).
Step 3:
Calculate total number of pints dehumidification equipment will
remove based on
Association of Home Appliance Manufacturers (AHAM)
test conditions at 80° F / 60% Rh.
Step 4:
Based on AHAM performance per 24 hours, the total
dehumidification needed should be calculated by dividing the
factor into the total cubic feet of the area being dried as
shown in
Table 7-I.
The Classifying of water damages as explained in this section
should only be a starting point based on the loss site
evaluation and conditions. Adjustments should be made as
determined by daily drying records and loss site conditions as
they change.
7.43) Heat (convection) Drying Systems:
As described in
Section 7.11.a, temperature could be considered the balance
point of a drying system, since moisture, water and the
materials that make up the built environment all react to heat.
When using
heat to mitigate (dry) a structure, the interior atmospheric temperature should
be maintained between 95° F to 105°
F. While interior atmospheric temperatures
maintained at 105°
F to 110°
F, when properly set-up and monitored
should reduce drying time. (ref. Section
7.43.c)
Convection (heat) drying systems can reduce structural drying time by 10% to 30%
at minimum, depending on what is wet?, the materials saturation and
the experience the drying technician has with the drying system,
as well as with the built environment that is being dried.
For a heat drying system to be efficient and prevent secondary
damages,
air movement and
air exchanges should be part of the
heat systems
equation:
Forced
Convection
=
Heat + Air Movement + Air Exchanges
The heat drying process should operate as a convection system,
where the moisture is transported to the exterior of a structure
through air changes.
When drying with heat, 3 to 4 air exchanges per
hour is recommended. Moreover, uniform heat throughout a
wet structure is recommended during the drying process, and
supplemental low grain dehumidifiers should be used to gain
uniformity, when required.
7.43.a) Net-Positive Pressure:
Since moist air will travel to dry air, when it can. Heat
drying systems should maintain a net-positive pressure during
the drying process when the specific humidity produced by the
drying system is lower than the relative humidity at the
exterior of a structure, which would produce excess infiltration
if the drying system is not properly balanced. (ref.
7.15.a)
7.43.b) Heat Precautions:
Temperatures in excess of 95°
F, when used to dry a structure, would require a pre-evaluation of
the property being heated to determine what may or may not be
affected by heat.
Items such as painting, pictures, books, candles, musical
instruments, antiques, etc. should be classified at low heat
sensitive and should be protected or removed during the heat
drying process.
When ducting heat, flexible ducting should be insulated to
prevent damage to grass, shrubbery, window sashes, doorways,
etc.
Fire suppression systems (i.e.,
fire sprinkler,
halon,
fire alarms &
smoke detectors, etc.) could require protective means or be
disarmed before the heat drying process begins.
Before a fire suppression system is altered, protected or
disarmed, the local fire authority, manufacturer of the fire
suppression system and all
occupants of the building should be notified.
When using heat drying systems, the manufacturers use practices,
safety precautions, and heat sensitive materials listing should
be followed.
Heat drying system manufacturers and technicians are encouraged
to develop a universal materials heat sensitivity chart
for the mitigation, remediation and restoration industries.
-
7.43.c) Drying System:
The following firms offer heat drying systems:
-
Aquadry Systems, LLC
-
Ground Heaters, Inc.
-
TES Drying System
-
ThermaPureHeat
-
Water Out
7.43.d) Other Heat Applications: Due to the
characteristics of heat --- heat systems can also be used as:
- Supplemental system to kill mold spores, in lieu of
disinfectants(1) (2)
- Pasteurization for treating bacteria, in lieu of disinfectants
(2)
- Document drying system, when documentation is wet/flooded due
to sewage back-flow (2)
- Extermination, in lieu of pesticides (2)
- Odor removal (3)
(1) Does not supplement the physical removal of mold spores.
(2) An industrial hygienist should always be consulted when
using heat for mold, bacteria, sewage or extermination.
(3) Does not supplement the physical removal of the odor source.
When using heat for disinfecting, the contaminate being
treated would
determine the heat reaction time required.
For additional information on using heat for other processes,
see Section 8.0. (coming soon)
Water
(drying): Page
Previous -
1 -
2 -
3
-
4 -
5
Extracted from the Loss
Recovery Guide with Standards (LRGS)
© Copyright 1998-2008 William Yobe
[Top
of Page]
|