|
6.0) FIRE and SMOKE:
(page 3 of 6)
6.17.f)
Molecule Formation of Ferrous Metals:
Ferrous metals when impacted with hydrogen
chloride or when affected by repeated hydrochloric acid will
change the molecule formation of the metal over time. This can
result in the corrosion process to be irresolvable if not
treated in a proper and timely fashion.
Ferrous metals have
equilibrium of electrical current or EMF’s.
As an Example:
Iron (Fe) produces both positive (+) and
negative (-) volts (Eº) which are called half-cells. When the
half-cells’ electrical currents are equal, corrosion should not
form:



When
ferrous metals are exposed to HCl and moisture, they break up
into ions; hydrogen (H) has a positive charge (+) and chloride (Cl)
has a negative charge (-). When the HCl molecules form into
ions, the hydrogen ion is lost to the water molecule, which
moves between the chloride and the water acting as the acid and
the base. This reaction of HCl ions causes an over voltage to
one of the iron half-cells causing free energy and corrosion
(rust) will form:


This free energy or excess EMF’s to the half-cell
causes the right-angled molecule of the iron to align, which
causes internal strain to the metal.
When the molecules of metal are aligned, the metal surface could
require a vigorous agitation or pounding action before the metal
would be completely neutralized of the HCl. A vigorous pounding
as produced from blasting, or 4 to 14 gallons per minute of
water pressure per the
SSPC would be needed to un-align the
metals molecules back to their right angles.
Acids have varying strengths and reactions to metals, fabrics,
etc. An acid strength is based on the number of hydrogen
ions that have transferred to the base. Weak acids
transfer a fraction of the ions of strong acids as shown in
Table 6-D --- highlighting acid strengths in aqueous solution at room temperature.
Acid
|
Strength
|
|
HCl
|
Very Strong |
|
HNO3 |
--- |
|
N2SO4 |
Very Strong |
|
HSO4 |
--- |
|
HF |
Weak |
|
C6H5COOH |
--- |
|
N2S |
Weak |
|
HCO3 |
--- |
|
H2O |
Very Weak |
Acid Strength in Aqueous Solution
At Room Temperature
Source: William Yobe & Associates
Table 6-D
6.17.g) Electrical Equipment and Wiring:
The
National Electrical Code®, NEC®
addresses soot, dirt, heat, chemical, gases, fumes and vapors in
several Articles as listed below:
- "The principal cause of insulation failures are heat,
moisture, and dirt. Insulation can also fail due to chemical
attack, mechanical damage, sunlight, and
excess voltage stresses." (NEC-HANDBOOK,
Article 110-7)
- "Unless identified for use in the operating environment, no
conductor or equipment shall be located in damp or wet
locations; where exposed to gases, fumes, vapors, liquids, or
other agents having a deteriorating effect on the conductor or
equipment; or where exposed to excessive temperatures." (NEC,
Article 110-11)
- "Internal parts of electrical equipment, including
busbar,
wiring terminals, insulators, and other surfaces shall not be
damaged or contaminated by foreign matter such as paint,
plaster, cleaners, abrasives, or corrosive residues. There
shall be no damaged parts that may adversely affect safe
operation or mechanical strength of the equipment such as parts
that are broken; bent; cut; or deteriorated by corrosion,
chemical action, or overheating." (NEC, Article 110-12
(c).
Reprinted with permission from NFPA 70-1999, the National
Electrical Code®, Copyright© 1998,
National Fire Protection Association, Quincy, MA.
This reprinted material is not the complete and official
position of the National Fire Protection Association, on the
referenced subject which is represented only by the standard in
its entirety.
National Electrical Code®
and NEC® are registered
trademarks of the
National Fire Protection Association, Quincy, MA.
Electrical apparatus and equipment when mounted within rain
tight or explosive proof housing should be protected from PIC's
and should not require mitigation of their interior components.
Exposed NM cable (romex), open feeders, devices, appliance and
equipment cords should be wiped clean. While motors, panels,
disconnect switches, terminal strips,
circuit board, etc. not
enclosed in rain tight or explosive proof housing should receive
appropriate neutralizing in and out when affected with hydrogen
chloride or hydrochloric acid. The cleaning method, and to what
level chlorides and sulfates should be reduced should be
confirmed with the apparatus and/or equipment manufacturer.
Electrical wiring insulation could be constructed
of plastics containing polyvinyl chlorides (PVC), which could be
neutralized using a mild detergent and water. All wiring
insulation should inspected for charring and heat
damage. When in doubt about a wire or motors’ integrity, an
infrared and/or insulation resistance test should be
performed.
Brushes, contactors, lugs, bugs, etc. when affected with
hydrochloric acids should be cleaned with an approved cleaner.
Motors, when affected with hydrogen chloride should be
electrically disconnected before cleaning, and should be cleaned
using methods approved by the manufacturer.
Regulated compressed air could be used to remove loose soot
deposits. When using compressed air on electrical equipment,
care should be taken not to drive or force soot and dirt
particles into windings, insulation, bearings, under tape, lugs,
etc.
Insulation used on motor and transformer windings, etc. could
contain synthetic fibers that could deteriorate when cleaned
with some solvents, causing premature electrical failure per
NEC, Article 110-11, FPN No. 2.
Moreover,
before using solvents, the manufacturer should be consulted.
Motors and equipment
bearings should be inspected for soot, smoke and corrosion,
since bearings can fail prematurely due to heat, moisture, dirt,
soot, rust and excessive (load) operating conditions. Heat can
also dissipate the lubrication on a bearing, allowing corrosive
materials to cause rusting to the low alloy liners within a
bearing housing, which are used to correct uneven rotation.
Bearing should be cleaned and lubricated as described in
Section 7.30.a.
Equipment or apparatus when manufactured with
ultrasonic welds should not be cleaned using ultrasonic methods
unless pre-approved by the manufacturer.
Insulation coverings should be dried-out or replaced before
re-energizing as described in
Section 7.30.
The testing of electrical equipment and/or apparatus should be
performed by or under the direct supervision of a competent
person.
All electrical power should be disconnected before attempting to
work on electrical equipment, apparatus, devices, wiring, etc.
When electrical equipment and apparatus are wet or under high
humidity attack, the procedures found in
Sections 7.30
and
7.30.a should apply.
6.17.h) Electronic Equipment: Electronic
equipment like electrical equipment is vulnerable to hydrogen
chloride gases, hydrochloric acid, soot and smoke.
Electronic equipment such as computers, televisions, stereos,
etc. have ventilating holes in their housing, which are an
access for smoke soot and gases to the inner electrical and
mechanical parts of the electronic equipment. The outer housing
of electronic equipment is generally constructed of plastics, or
metal with a plastic coating and both are vulnerable to
discoloration.
The repair, testing, cleaning, neutralizing or drying of
electronic equipment should be performed using the manufacturers
specifications, or Military Specification (Mil Spec) 28809A and
28809B as applicable should be used when manufacturers do not
have specifications in-place. While method of detergents,
chemicals and/or mechanical actions such as; regulated air,
ultrasonic, C02, soda ash or low-pressure washing is acceptable,
when approved by the manufacturer.
Operation manuals and manufacturers should be consulted
before disassembly begins, and technicians should refer to
serial and model numbers when consulting manufacturers.
Equipment manufactured with
ultrasonic welds, integrated circuits or semiconductors should
not be cleaned using ultrasonic methods unless pre-approved by
the manufacturer.
Electrical wiring
found in electronic equipment is generally heat resistant and
vulnerable to acid and soot attack, and should be rinsed after
cleaning with clean mineral free water and dried before
reassemble. The drying of electronic equipment should be
performed in a regulated environment.
When
neutralizing electronic equipment, the sodium chloride
equivalent (SCE) should be reduced to levels determined by the
electronic equipment manufacturer. When the electronic
manufacturer does not have SCE specifications in-place, the SCE
should be reduced to 20 mcg/per square inch as determined by
Military Specification (Mil-Spec) 28809A.
The repair, testing,
cleaning, neutralizing or drying of electronics should be
performed by or under the direct supervision of a competent
person.
When
moisture or water affect electronic equipment, they should be
disconnected at the power source.
Extracted from the Loss
Recovery Guide with Standards (LRGS)
© Copyright 1998-2008
William Yobe
|
Find
It Fast - With
The ...
LRGS
-
Navigational
Index
6.18) Surface Testing:
The deposit of smoke, soot and gases can affect
horizontal and vertical surfaces both structural and contents
within a single room, and these deposits could be spotty.
Smoke, soot and gases deposits could be black, brown, gray,
white or clear resulting in subjective opinions.
Subjective structural components, substrates and content items
should be tested to determine if smoke, soot, gases or
contaminates are present. Before testing begins,
technicians should determine the fuel source of the fire.
This would help in determining the methods and type of tests
needed. When the fuel source is acidic, the acidic
(sulfate and chloride) levels of structural metal surfaces
should be tested before and after mitigation or restoration
procedures as described in
Section 6.18.a.
6.18.a) Chloride Field Test:
The use of a chloride ion field test is an accurate method when determining acidic levels on
structural metals in the field. However, field tests when
positive, should be quantified using an
ion chromatography test.
Chloride field testing kits (Chlor*Test) can be purchased from CHLOR*RID International or
from
KTA-Tator.
6.18.b) Soot Testing: When
soot deposits in rooms and surfaces appear to be minor, spotty
or subjective, they should be tested using a cellulose dry
sponge, wipe or swab sample. When soot conditions are
undetectable to the naked eye, samples from the surface or the
surface itself should be examined with the aid of a
microscope.
When soot conditions
are subjective or not visible, testing maybe necessary for the
following reasons:
- As hot smoke and soot from a
burning fire meet cool air within
an adjoining room, an atmospheric reaction of
wavelengths
sends soot and smoke deposits throughout a structure.
As the smoke and soot cools, their effects can be
varying
on structural surfaces and content items.
- Soot is attracted to varying surfaces due to a temperature
differential. Cool surfaces will attract soot residues
before
warm surfaces. During winter months, soot deposits
could
be heavier on exterior walls. During summers months,
the
location of heavy soot deposits could vary based on the
time the fire started and the temperature of the
building
envelope and the placement of contents. Cabinet
and furniture interiors, when cooler than the air
within a structure could attract hot soot deposits.
- Atmospheric pressure caused from heated gases can force
soot and smoke within confined areas of a structure and
content items as well as affect the underside of
content items
- Smoke and soot deposits could be black, brown, gray, white
or clear.
6.19) Protein Fires: Misty
soot, as produced from a
protein
fire are attracted to and can infiltrate cool nooks,
crannies, as well as deposit within and beneath content
items. The micro-size of protein soot could result in property owners, adjusters and technicians to attempt a quick cleaning
process, which could fail.
The
decomposition of living organisms found in animal fats is
exotoxin
bacteria, and can be toxic and emit foul decaying
odors. Moreover, when left on painted surfaces can turn to a
beige-pink color in a short time, possibly requiring a full
restoration of cleaning, sealing and painting.
Surfaces with light soot deposits should be thoroughly cleaned
using a mild detergent, while heavy concentrated areas could
require strong degreasers. Careful detail should be addressed
to the interior and underside of contents, building components,
as well as nooks and crannies.
Food service and personal
hygiene surfaces should receive an
application of an approved disinfectant after cleaning.
Disinfectants should be
allowed adequate time to react and surfaces should be rinsed
with clean mineral free water after disinfectants have had
adequate time to react.
Detergent aromas could cover up protein odors
only to have them reappear. When protein
odors
reappear, the testing methods in Section 6.19.a should apply.
Affected
upholstery,
carpets and clothing should be cleaned, and disinfected when
necessary.
Protein fire mitigation is not a one-stop process, but a trial
and error process and could require several processes. Property
owners and adjusters should be made aware of all steps and
procedures before and during the mitigating process.
6.19.a) Protein Fire Testing: Protein
fires are from living organisms such as poultry and beef and
could produce a clear invisible misty soot that could be
unnoticeable to the naked eye.
Protein soot deposits can be tested by extracting a surface
sample using a non-alcohol wipe or swab and examined using a
microscope.
When baseboards and
casing have a stained finish, and a small gap is present, the
baseboard/casing should be loosened and samples taken from the
backside of the baseboard/casing and tested.
When odors persist after cleaning, certain areas
or building components should be encapsulated within plastic
sheeting for 24 to 48 hours, which can help narrow down the
affected (odor) areas.
The testing and evaluation of protein samples should be
performed by or under the supervision of a competent person.
6.20) Mitigation and Restoration Equipment:
The loss type, surface types and post-conditions
would determine the types and quantity of equipment needed to
mitigate or neutralize a loss site. See
Section 4.0 for a brief
listing of mitigation equipment.
6.20.a) Mitigation Equipment Inspection:
Equipment
left on site, in an operable state for a considerable amount of
time (overnight) should be inspected at minimum, once in a 24-hour
period.
This should include gas-powered equipment (generators),
airmovers, dehumidifiers, ozone generators, ULV foggers,
injection dryers, air scrubbers, etc.
6.21) Structural Surfaces: Structures
can contain varying surfaces:
- Walls and ceilings could be painted drywall or plaster.
Paneling could have a wood or photo finish. Tile
could be ceramic, metal or plastic.
- Wall coverings could be paper, vinyl or cloth. Casings
and baseboard could be painted or stained, soft
or
hardwood, or pre-finished vinyl.
- Doors and windows could be vinyl, painted or stained
wood, aluminum or steel.
-
Kitchen and bath counter tops could be
constructed
using ceramic tile, plastic laminate or hard
surface materials.
- Kitchen and bath fixtures could have chrome,
nickel or
gold plate, porcelain, fiberglass or acrylic
finish.
- Cabinetry could be constructed from veneer plywood,
hardwood (stained or painted) or powder coated
metal.
- Floor surfaces could be sheet or tile (VCT) vinyl, hard
or soft wood, glazed or non-glazed tile, marble
or carpet.
- Carpets could be constructed from natural wool, cotton,
silk, jute, or of synthetic nylons: 2nd,
3rd, 4th, 5th
generation, polyester, olefin, acrylic or rayon.
Based on the varying surfaces listed above, contractors should
stock a full range of chemicals and cleaning agents with respect
to their surface reaction, strengths, compounds and make-up
range as described in
Section 4.7.
Surfaces should be tested for reaction and colorfast before
applying chemicals.

Fire and
Smoke: Page
Previous -
1 -
2 -
3 -
4
-
5 -
6 -
Next
[Top
of Page]
|